Bộ điều khiển máy phát điện Deep Sea DSE7110 MKII DSE7110 MKIIAuto Start Control ModuleThe DSE7110 MKII is an Auto Start Control Module with an icon-based display. The control module has been designed to control single diesel or gas gen-set applications. OVERALL SIZE
240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”) PANEL CUTOUT SIZE 220 mm x 160 mm (8.7" x 6.3") MAXIMUM PANEL THICKNESS 8.0 mm (0.3”) WEIGHT 0.82kg PRODUCT VARIANTS 7110-01 - 7110 MKII Auto Start Control Module |
|
Lượt xem: | 10605 |
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
290 mA at 12 V, 140 mA at 24 V
MAXIMUM STANDBY CURRENT
75 mA at 12 V, 40 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt-free)
AUXILIARY OUTPUTS E, F, G & H
2 A DC at supply voltage
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.